Free Engineering Calculator

Chiller Performance Calculator

Calculate COP, efficiency (kW/ton), condenser and evaporator heat duty, approach temperatures, fouling resistance, and water treatment diagnostic flags for centrifugal, screw, and absorption chillers — fully client-side, no data sent to any server.

18
Calculations
3
Chiller Types
US/SI
Unit Toggle
100%
Client-Side
Unit System
← All Free Tools

Section 1 of 6

Chiller Configuration

Select chiller type, compressor drive, and nominal capacity. These selections drive refrigerant cycle inputs and applicable efficiency benchmarks.

Chiller Type & Capacity

Section 2 of 6

Condenser Water

Enter condenser water temperatures and flow rate. These values drive heat rejection duty, condenser approach temperature, and water-side fouling analysis.

Condenser Water Temperatures

Section 3 of 6

Evaporator (Chilled Water)

Enter chilled water supply and return temperatures and flow rate. These values determine cooling capacity, evaporator duty, and chilled water approach temperature.

Chilled Water Temperatures

Section 4 of 6

Refrigerant Cycle

Enter refrigerant saturation temperatures or pressures. These drive compressor lift, condensing and evaporating approach temperatures, and COP calculations. All inputs are optional — calculations will use water-side temperatures when refrigerant data is absent.

Saturation Temperatures

Compressor Power & Approach Temperatures

Section 5 of 6

Known Performance optional

Enter datasheet or design-rated values to calculate cleanliness factors and fouling resistance for both condenser and evaporator. Compare actual performance to design and detect fouling degradation.

Design / Datasheet Values

Section 6 of 6

Calculate & Results

Click Calculate to run all available computations. Blank optional inputs are skipped — the calculator computes what it can from the data provided.

Performance Summary

Section 7 of 7

Formulas & References

Engineering basis for all calculations performed by this tool.

Cooling Capacity

Evaporator Heat Duty (Cooling Capacity)

Q_evap = GPM × 500 × ΔT_chw [BTU/h] (US)
Q_evap = (L/s) × 4.187 × ΔT_chw × 3600 [kJ/h] (SI)

Where ΔT_chw = CHWRT − CHWST. Constant 500 = 8.34 lb/gal × 60 min/h × specific heat ≈ 1.0 BTU/lb·°F for water.

Refrigeration Ton Conversion

Tons = Q_evap [BTU/h] / 12,000

One refrigeration ton = 12,000 BTU/h = 3.517 kW. Heat rejection duty: Q_cond = Q_evap + W_comp.

Efficiency Metrics

Coefficient of Performance (COP)

COP = Q_evap [kW] / W_comp [kW]

For vapor-compression chillers. A higher COP indicates better efficiency. Single-stage absorption chillers have COP ≈ 0.6–0.8; double-stage ≈ 1.1–1.4.

Energy Efficiency Ratio (kW/ton)

kW/ton = W_comp [kW] / Q_evap [tons]

Lower kW/ton = better efficiency. ASHRAE 90.1 full-load benchmarks: centrifugal ≤ 0.634 kW/ton (water-cooled); screw ≤ 0.780 kW/ton. IPLV targets are typically 10–20% lower.

Carnot COP & Isentropic Efficiency

COP_Carnot = T_evap_K / (T_cond_K − T_evap_K)
η_isentropic = COP / COP_Carnot

Temperatures in Kelvin (K = °F + 459.67) / 1.8. Typical isentropic efficiency for well-maintained centrifugal: 55–70%.

Heat Transfer — Condenser & Evaporator

Condenser Heat Duty

Q_cond = Q_evap + W_comp [BTU/h or kW]

Heat balance: all compressor work is rejected as heat plus the absorbed evaporator load. For absorption chillers, W_comp is replaced by heat input Q_generator.

LMTD — Condenser & Evaporator

LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁ / ΔT₂)

For condenser (counterflow): ΔT₁ = T_ref_cond − ECWT; ΔT₂ = T_ref_cond − LCWT.
For evaporator (counterflow): ΔT₁ = CHWRT − T_ref_evap; ΔT₂ = CHWST − T_ref_evap.

Approach Temperature

Approach_cond = T_ref_condensing − LCWT
Approach_evap = CHWST − T_ref_evaporating

Design condenser approach: 8–12°F (4.4–6.7°C). Design evaporator approach: 5–8°F (2.8–4.4°C). Values exceeding design by >3°F indicate fouling or scaling on water-side surfaces.

Overall Heat Transfer Coefficient (U)

Q = U × A × LMTD
U_calc = Q / (A × LMTD)

A = N_tubes × π × OD × L × passes. U is then compared to datasheet U to compute cleanliness factor and fouling resistance.

Cleanliness Factor & Fouling Resistance

CF = (U_calc / U_design) × 100 [%]
Rf = (1/U_calc) − (1/U_design) [h·ft²·°F/BTU]

CF below 85% typically indicates significant fouling. TEMA allowable Rf for treated cooling water: 0.001 h·ft²·°F/BTU. Values > 0.002 indicate actionable fouling on either condenser or evaporator surfaces.

Compressor Lift & Refrigerant Cycle

Compressor Lift

Lift = T_condensing − T_evaporating [°F or °C]

Lift is the primary driver of compressor energy consumption. Every 1°F increase in condensing temperature increases energy consumption by approximately 1.5–2%. Every 1°F decrease in evaporating temperature increases consumption by approximately 1.5%. Fouling-driven approach temperature increases directly elevate effective lift.

Efficiency Benchmarks
Chiller TypeFull-Load kW/tonCOP RangeASHRAE 90.1 Limit
Centrifugal (water-cooled)0.45–0.705.0–7.8≤ 0.634 kW/ton
Screw / Scroll (water-cooled)0.65–0.854.1–5.4≤ 0.780 kW/ton
Absorption (single-stage)N/A (heat-driven)0.60–0.80COP ≥ 0.70
Absorption (double-stage)N/A (heat-driven)1.10–1.40COP ≥ 1.00
Fouling Impact on Chiller Efficiency

Efficiency Penalty from Condenser Fouling

ΔkW/ton ≈ 1.5–2.0% per 1°F rise in condensing temperature

Each 0.001 h·ft²·°F/BTU of condenser fouling resistance raises the condensing saturation temperature approximately 1–2°F, increasing compressor power by 1.5–2.0%. ASHRAE research (RP-884) confirms that condenser fouling is the most common cause of chiller efficiency degradation in operating plants.

References: ASHRAE Handbook — Refrigeration (2022); ASHRAE Standard 90.1-2022; AHRI Standard 550/590; ARI Standard 560 (absorption); TEMA Standards 10th Ed.; Engineering Toolbox.