Free Diagnostic Tool

Cooling Water Program Analyzer

Enter your makeup and system water analyses to assess cycles of concentration, scale risk at heat transfer surfaces, and corrosion risk — in under 2 minutes.

This tool provides a first-principles screening assessment. It does not replace saturation modeling software or a full program review.

Unit Settings

Select your preferred input units before entering water analyses.

Water Analysis

Enter your makeup (source) and cycled (system) water analyses. Enter 0 or leave blank for unmeasured parameters.

Ion Reported As Note Makeup Water
(mg/L)
Cycled Water
(mg/L)
Calcium as CaCO₃
Magnesium as CaCO₃
Total Alkalinity (M-Alk) as CaCO₃ Bicarbonate + Carbonate
Chloride as Cl⁻
Sulfate as SO₄²⁻
Silica as SiO₂
Iron (Total) as Fe
Phosphate (Total) as PO₄ Leave blank if not measured
Sodium as Na⁺
Potassium as K⁺ Optional
TDS mg/L (always) Optional — used for cross-check only
pH standard units Required for LSI / RSI

Temperature

LSI/RSI are calculated at skin (heat transfer surface) temperature. Silica saturation is calculated at cold water basin temperature — where amorphous silica is least soluble.

If unknown, add 20°F (11°C) to exit temperature above. Skin temperature drives CaCO₃ scale risk — not bulk water temperature.
Used for silica saturation. Amorphous silica is normally soluble — it precipitates at the coldest point in the system. Defaults to 75°F (24°C) if not entered.

Program Questions

Answer to enable accurate CoC consistency checks and contextual warnings.

Do you feed acid for pH control?
Do you feed chlorine or a chlorine derivative (bleach, BCDMH, trichlor, stabilized chlorine, etc.) as a biocide?
Do you feed any inorganic, complex, or organic phosphate as a corrosion/scale inhibitor?

All calculations are performed locally in your browser. No data is stored or transmitted unless you request a free review.

Analysis Results

Summary Flags & Warnings

Cycles of Concentration

CoC calculated per ion. Conservative (non-precipitating) ions — Cl, SO₄, Na — establish the reference CoC. Deviations ≥5% in reactive ions indicate potential precipitation or other consumption.

Ion Makeup (mg/L) Cycled (mg/L) CoC Notes / Flags

LSI at Skin Temperature

−3 — CaCO₃ Dissolving 0 (balanced) +3 — CaCO₃ Scaling / Precipitation

Ryznar Stability Index (RSI)

Silica Saturation Assessment

Evaluated at cold water basin temperature — amorphous silica is normally soluble (precipitates at lowest system temperature, not at heat transfer surfaces).

Magnesium Silicate Saturation Risk

Industry index: Mg(as CaCO₃) × SiO₂. Inversely soluble with temperature and pH. SI = log₁₀(product / pH threshold) — SI > 0 indicates precipitation risk. Thresholds: 12,000 (pH 7.5–8.5) and 3,000 (pH > 8.5) per Meyers IWC-99-64.

Calcium Magnesium Silicate Saturation Risk

Industry index: (Ca+Mg)(as CaCO₃) × SiO₂. Inversely soluble with temperature and pH. SI = log₁₀(product / 50,000) — risk is pH-gated: no flag below pH 8.4, caution 8.4–8.6, elevated risk above pH 8.6.

Calcium Sulfate Saturation Risk

Saturation Ratio (SR) = [Ca²⁺][SO₄²⁻] / Ksp. Evaluated at skin temperature — gypsum solubility decreases with temperature above ~40°C. SR > 0.8 warrants attention; SR > 1.0 indicates precipitation risk.