Technician inspecting the open condenser waterbox of a centrifugal chiller
CASE STUDY · COMMERCIAL HVAC · CHILLER DIAGNOSTICS

An energy consultant said replace the chiller. The panel data said clean it.

~$450K cost avoided · Approach 4.6 → 1.9 °F
~$450K
Replacement cost avoided
~8×
Rated fouling allowance found
4.6 → 1.9 °F
Condenser approach restored
0 labs
Diagnosed from panel data

What this case study covers

A commercial office tower was about to replace a 500-ton centrifugal chiller on an energy consultant’s recommendation. A structured diagnostic using only data the chiller already reports proved the problem was waterside biofilm at roughly eight times the rated condenser fouling allowance, caused by a pump VFD retrofit that dropped tube velocity below the OEM minimum. The machine was cleaned, the cause corrected, and the replacement cancelled.